Course Home Page

2008 NEC Changes Test 4

Course Name:  2008 NEC Changes
Quiz Number:  No.4
Teacher:  Gerald Newton
Teacher's Email:  electrician@electrician2.com

No. of Questions= 10


1 210.4 Multiwire Branch Circuit (B) revised. Each multiwire branch circuit shall be provided with a means that will simultaneously disconnect all ungrounded conductors at the point where the branch circuit originates. Note: Many handle ties are not UL approved and may not be allowed for fulfilling this requirement.

Question: A multiwire branch circuit shall be provided with a disconnecting means that _________________________all ungrounded conductors at the point where the circuit originates.

a) disconnects
b) simultaneously disconnects
c) opens
2 210.4(D) Grouping. (This is a new requirement) The ungrounded and grounded conductors of each multiwire branch circuit shall be grouped by wire ties or similar means in at least one location within the panelboard or other point of origination. Exception: The requirement for grouping shall not apply if the circuit enters from a cable or raceway unique to the circuit that makes the grouping obvious.

Question: Ungrounded conductors and grounded conductors of multiwire branch circuits shall be _________ in a least one location within a panelbaard unless the grouping is obvious.

a) bundled
b) tie wrapped
c) grouped
3 210.5(C) (Revision) Ungrounded Conductors. Where the premises wiring system has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor of a branch circuit shall be identified phase or line and system at all termination, connection and splice points. Note: "accessible" was replaced with termination, connection, and splice points.

Question: If a 480 volt and a 208 volt system are on the same premises then each is required to be identified by phase or line and system at _____ termination, connection and splice points.

a) Some
b) All
c) Accessible
4 210.8(A)(2) & (A)(5) Exceptions No. 1 and 2 Deleted. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in (1) through (8) shall have ground-fault circuit-interrupter protection for personnel. The exceptions for not readily accessible and the exception for a single receptacle or a duplex receptacle for two appliances located within dedicated space for each appliance that, in normal use, is not easily moved from one place to another and that is cord-and-plug connected have been deleted. There are still two exceptions included. One is for receptacles located outdoors for snow melting equipment that are not readily accessible, and the other is for unfinished basements for permanently installed fire or burglar alarm systems. Others than these two exceptions all receptacles installed in bathrooms, garages and accessory buildings with a floor at or below grade level, crawl spaces, receptacles in kitchens that serve countertop surfaces, laundry facilities and wet bar sinks where the receptacle is within 6 feet of the outside edge of the sink, and boathouses are required to have GFCI protection.

Question: In general, in dwelling units receptacles installed in the following locations are required to have GFCI protection.

a) bathrooms
b) garages
c) outdoors
d) kitchens
e) All of the above
5 210.8(A)(2) & A(5) Exceptions No. 1 and 2 Deleted
All 125-volt, single-phase 15 and 20 ampere receptacles in dwelling unit garages, accessory buildings, and basements are required to have ground-fault circuit-interrupter protection.
Appliances built to new product standards have 0.5 mA leakage or less. This is far below the 4 to 6 mA required to trip a Class A GFCI.

Question:  All 125-volt, single-phase 15 and 20 ampere receptacles in dwelling unit garages including those for garage door openers and freezers, accessory buildings, and basements are required to have ________________ .

a) arc-fault circuit interrupter protection
b) ground-fault circuit-interrupter protection.
6 210.8(B) Other Than Dwelling Units. This section has been revised to now requires that All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in (1) through (4) shall have ground-fault circuit-interrupter protection for personnel: (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors
Exception No. 1 for dedicated branch circuits for electrical snow melting or deicing equipment remains, and a new Exception No. 2 has been added. Exception No. 2 For outdoor receptacles in industrial establishments where conditions of maintenance and supervision ensure that only qualified personnel are involved an assured equipment grounding program shall be permitted for only those receptacle outlets used to supply equipment that would create a greater hazard if power is interrupted or having a design that is not compatible with GFCI protection.

Question: For non dwelling units except for out of doors' snow melting or deicing equipment and in nonindustrial locations, receptacles located in the following locations shall have GFCI protection.

a) Bathrooms
b) Kitchens
c) Rooftops
d) Outdoors
e) All of the above
7 210.8(B)(5) Other Than Dwelling Units New exception added. Receptacles installed with 6 feet of the outside edge of a sink are required to have GFCI protection. The new Exception states: For receptacles located in patient care areas of health care facilities other than those covered under 210.8(B)(1) [for bathrooms], GFCI protection shall not be required.

Question: For other than dwelling units receptacles located within _______ feet of a sink or in bathrooms are required to be GFCI protected except for receptacles located in patient care areas and health care facilities or some industrial laboratories.

a) 3
b) 6
c) 10
8 210.8(B)(5) Exception No. 1 to 5. Other than Dwelling Units - Sinks. In general receptacles located within 6 feet of the outside edge of a sink are required to be GFCI protected. This new exception exempts receptacles from being GFCI protected if they are located in industrial laboratories used to supply equipment where removal of power would introduce a greater hazard.

Question: In industrial facilities receptacles within 6 feet of the outside edge of a sink that supply equipment that might present a hazard if power is removed ______ have to be GFCI protected.

a) do not
b) do
9 210.8(C) Boat Hoists. GFCI protection shall be provided for outlets not exceeding 240 volts that supply boat hoists installed in dwelling unit locations. This section previously only required protection for 125-volt 15- and 20- ampere branch-circuits supplying boat hoists. Note: This revision requires all OUTLETS to be GFCI protected, not just receptacles.

Question: All _______ not exceeding 240 volts that supply boat hoists in dwelling unit locations shall be provide with GFCI protection.

a) receptacles
b) outlets
10 210.12(B) Arc-Fault Circuit-Interrupter Protection. Listed combination-type AFCI-protective devices are now required in all dwelling unit rooms, except for kitchens, bathrooms, laundry rooms, garages, basements, and rooms or areas not specified in this section.
This section reads: Dwelling Units All 120-volt, single phase, 15- and 20- ampere branch circuits supplying outlets installed in dwelling unit family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms,am closets, hallways, or similar rooms or areas shall be protected by a listed arc-fault circuit interrupter combination-type installed to provide protection of the branch circuit.

Question: AFCI protection is required for all 120-volt single phase, 15- and 20- ampere branch circuits supplying outlets installed in dwelling units except for ________ .

a) kitchens
b) bathrooms
c) laundry rooms
d) garages and basements
e) All of the above





Go to top of quiz
© Gerald Newton