Motor Circuit Conductor and Voltage Drop Calculator (BETA Version) electrician.com (60 HZ Alternating Current induction type 1-phase & 3-phase, wound rotor, and under 600 volt motors ) |
|
Motor AC Voltage | Horsepower (Notes 5 - 9) | Phase (Notes 5 - 9) | Type of Motor (Note 10) | Class of Service (Notes 1 & 2) | Duty-Cycle Service (Notes 1 & 2) |
| | | | | |
Enter NamePlate Current Required If Class of Service is other than Continuous. Optional otherwise. Note 21 | Conductor Material | Ambient Temperature C | Number Current Carrying Conductors in Raceway or Cable or bundle |
Service Factor is 1.15 or greater | Special Conditions |
Temp rise is not over 40 Degrees C. |
Select Conductor Insulation Temperature Note 22 | Select Termination Temperature C. | Circuit conductors are bundled or in raceway 24 inches or less in length | Conductors are in Type AC or MC cable that complies with Note 3. |
Yes | | Yes | |
No | | No | |
CLICK BUTTON FOR OUTPUTS BELOW |
|
Conductor Size | Motor branch-circuit short-circuit and ground-fault protection (percentage of FLA from Tables 430.248 and 430.250) |
1-phase and 3-phase squirrel cage motor outputs |
Equipment Grounding Conductor Size (Note 23) | non time delay fuse (300% ) | dual element time delay fuse (175%) | instantaneous trip circuit breaker (800% or 1100% -design B) | inverse time trip circuit breaker (250%) |
| | | | |
Absolute Maximum Values see Note 11 |
Motor Disconnect Size (Note 17) amperes minimum or hp rated switch (min) | a) 400% for fuses not greater than 600 amperes b) 300% for fuses of 601 to 6000 ampere classification Notes 12 & 16 | 225% Note 13 | 1300% 1700% for Design B Note 14 | a) 400% for FLA of 100 amperes or less b) 300% FLA is greater than 100 amperes Note 15 |
NEMA Information Controller size Notes 18, 19, 20, & 24 Terminal Size Note 25 |
Overload Protection (Note 21) normal max size 430.32 max relay size 430.34 | | | | |
Wound Rotor Motor outputs |
non time delay fuse ( 150%) | dual element time delay fuse (150%) | instantaneous trip circuit breaker (800%) | inverse time trip circuit breaker (150%) |
| | | |
Data |
Conductor Derated ampacity
| Terminal Ampacity
| AC or MC Cable Derating Factor (if applicable) | Ambient Correction Factor
|
Total Load
| Terminal Load (total load)
| Full Load amperes (FLA)
| Conductor Derating Factor for more than three current carrying conductors
|
Conductor ampacity
| Conductor circular mil area
| Total conductor ampacity Derating Factor
|
| Motor Full Load Amperes Current Multiplier (for continuous duty Class of Service)
| Nameplate current multiplier (for other than continuous duty Class of Service ) see Note 4 |
| | | Voltage Drop for above Conductors | Enter Distance, Then Click Calculate Button (If available, this calculator uses nameplate FLA as a load. Otherwise the Motor FLA from the NEC Tables is used.) | Enter Distance infeet from supply to load (one way)
| | Input from above program: | Material | Volts/Phase | conductor Size | CMA of conductor | Load (FLA or Nameplate) | k (circular mil-ohm ft. | | | | | | | | Voltage drop
| Voltage at load end of circuit
| Per Cent voltage drop
| | | | | Copyright Notice | Notes | 1. Any motor application shall be considered as continuous duty unless the nature of the apparatus it drives is such that the motor will not operate continuously with load under any condition of use. 2. See Table 430.22(E) for more information on Classification of Service. 3. 310.15(B)(2)(3)(a)Exception No, 5 Circuit is Type AC cable or to Type MC cable without an overall outer jacket under the following conditions:(1) Each cable has not more than three current-carrying conductors. (2) The conductors are 12 AWG copper.(3) Not more than 20 current-carrying conductors are bundled, stacked, or supported on “bridle rings. (Load must be 18.6 amperes or less - ambient multiplier 1.04 x .6 x 30)) 4. Table 430.22(E) lists Duty-Cycle Service descriptions. 5. Single phase motor horsepower shall be from 1/6 hp to 10 hp and 115 volts to 230 volts. 6. Three phase horsepower shall be from 1/2 hp to 500 hp. 7. Three phase 115 volt motors shall be 1/2 hp to 2 hp. 8. Three phase Motors from 3 hp to 200 hp shall be 200 volts to 575 volts. 9. Three phase Motors from 250 hp to 500 hp shall be 460 volts or 575 volts. 10. Single Phase Motors cannot be design B or wound rotor types. 11. 430.52(C)(1) Exception No. 2 Where the rating specified in Table 430.52, as modified by Exception No. 1, is not suffıcient for the starting current of the motor: notes 12 thru 16 apply. 12. The rating of a nontime-delay fuse not exceeding 600 amperes or a time-delay Class CC fuse shall be permitted to be increased but shall in no case exceed 400 percent of the full-load current. See Note 15 below. 13. The rating of a time-delay (dual-element) fuse shall be permitted to be increased but shall in no case exceed 225 percent of the full-load current. 14. Where the setting specified in Table 430.52 is not suffıcient for the starting current of the motor, the setting of an instantaneous trip circuit breaker shall be permitted to be increased but shall in no case exceed 1300 percent of the motor full-load current for other than Design B energy-effıcient motors and no more than 1700 percent of full-load motor current for Design B energy-effıcient motors. Trip settings above 800 percent for other than Design B energy-effıcient motors and above 1100 percent for Design B energy-effıcient motors shall be permitted where the need has been demonstrated by engineering evaluation. 15. The rating of an inverse time circuit breaker shall be permitted to be increased but shall in no case exceed 400 percent for full-load currents of 100 amperes or less or 300 percent for full-load currents greater than 100 amperes. 16. The rating of a fuse of 601–6000 ampere classification shall be permitted to be increased but shall in no case exceed 300 percent of the full-load current. 17. The disconnecting means for motor circuits rated 600 volts, nominal, or less shall have an ampere rating not less than 115 percent of the full-load current rating of the motor, or be a listed nonfused motor-circuit switch having a horsepower rating not less than the motor horsepower. 18. The controller shall be a horsepower rated switch, general use switch for motors up to 2 hp and 300 volts, or an inverse time circuit breaker. 19. Motors 1/8 hp and less do not require a separate controller. The branch-circuit protective device shall be permitted to serve as the controller. 20. For portable motors rated at 1⁄3 hp or less, the controller shall be permitted to be an attachment plug and receptacle. 21. Nameplate full load amperes is used to calculate the overload protection size. The overload protection size will result in an output of "N/A" if the nameplate full load current is not entered. The nameplate full load current value is required for other than continuous class of service since this value is used to calculate the branch-circuit ground-fault and short-circuit protection device values. 22. NM cable shall have a 90 degree C insulation (used for derating) but shall be used at the 60 degree C ampacity (334.80). (Use 90 degree C insulation and 60 degree C termination ampacity.) 23. If the motor circuit overcurrent device consists of an instantaneous trip circuit breaker or a motor short-circuit protector, as allowed in 430.52, the equipment grounding conductor size shall be permitted to be based on the rating of the motor overload protective device using Table 250.122. If the nameplate full load current value is not entered this determination cannot be made. In this case "N/A" shall appear in the output box for the equipment grounding conductor. 24. NEMA sizes are from NEMA ICS 2-2000 Tables 2-4-1 and 2-4-2. Results for NEC Motor horsepower, phase, and voltage combinations found in NEC Tables 430.248 and 430.250 for which there are no NEMA listing are given as "N.L." 25. From NEMA ICS 2-2000. For controller size 5 and larger, a combination of parallel conductors that provide the ampacity equivalent to the wire sizes shown shall be permitted. Terminal sizes are given for 60 degree and 75 degree insulations. Where values are not listed in Table 1-7-1the result will be "N.L." Where the insulation is 90 degrees C. the terminal values are given for 75 degree C insulations. 60 degree C. terminal sizes are given for NEMA controller sizes "00" to 3. 75 degree C. terminal sizes are given for controller sizes "00" to 7. |
|
|