Required Minimum time to complete this Test is 20 minutes or 1,200 seconds.
This Test cannot be submitted for grading if cumulative time is less than 1,200 seconds.
 
Course Home Page

2014 NEC Changes Test 3

Course Name:  2014 NEC Changes 
Quiz Number:  No. 3
Teacher:  Gerald Newton
Teacher's Email:  electrician@electrician2.com
Student Name:    
Student Email:   


No. of Questions= 10
Pass mark is - 70 %.

To submit this test, press the Submit button at the bottom of the page after Cumulative elapse timer reaches 1,200 seconds
.


1

If a listed supplemental arc protection circuit breaker is installed at the origin of the branch circuit in combination with a listed outlet branch circuit type AFCI installed at the first outlet box on the branch circuit the AFCI device shall be within ______ ft of the circuit breaker when using No. 12 AWG conductors.

 
a) 25
b) 50
c) 70
2 If a listed outlet branch circuit type AFCI is installed at the first outlet in combination with a listed branch circuit overcurrent protective device the AFCI device shall be installed within _____  of the branch circuit overcurrent device when using No. 14 AWG conductors.
a) 25
b) 50
c) 70
3 A listed branch-circuit type AFCI device (first outlet) is permitted with ________________, Type MC, steel armored AC cables, metal wireways, metal auxiliary gutters, or metal outlet and junction boxes installed for the portion of the branch circuit between the OCPD and the first outlet.
a) ENT, Flexible Metal Conduit
b) EMT, RMC, IMC
c) PVC Schedule 80 conduit
4 Where a listed metal or nonmetallic conduit or tubing or type MC cable is encased in not less than ____ inches of concrete for the portion of the branch circuit between the OCPD and the first outlet, it shall be permitted to install a listed branch circuit type AFCI at the first outlet.
a) 2
b) 4
c) 6
5 AFCI protection shall not be required where the extension of the existing conductors is not more than _____ and does not include any additional outlets or devices.
a) 2 ft.
b) 20 ft.
c) 6 ft.
6 All 120-volt, single-phase, 15- and 20- ampere circuits supplying outlets in dormitory unit bedrooms, living rooms, hallways, closets, and similar rooms shall be protected by _________________________ .
a) arc-fault circuit interrupters  
b) Ground Fault Circuit Interrupters
c) combination AFCI/GFCI circuit interrupters
7 Each branch circuit disconnect rated 1000 amperes of more and installed on solidly grounded wye electrical systems of more than 150 volts to ground, but not exceeding 600 volts phase to phase shall be provided with ground fault protection of equipment in accordance with the provisions of 230.95 with the exception of:
a) industrial processes requiring an orderly shutdown.
b) where GFP is provided on the supply side of the branch circuit and on the load side of any transformer supplying the branch circuit.
c) a or b
8

Outlets installed for the purpose of charging electric vehicles shall be supplied from a _____________ .

 
a) the same circuit that is used for a work bench
b) separate branch circuit
c) multiwire branch circuit
9

Balconies, decks, and porches that are attached to the dwelling unit and are accessible from inside the dwelling unit shall have at least one receptacle outlet accessible from the balcony, deck, or porch.

The receptacle outlet shall not be more than _____ above the balcony, deck, or porch walking surface.

 
a) 6 ft.
b) 18 inches
c) 2 ft.
10

At least one receptacle outlet shall be installed at each dwelling unit attached garage or detached garage with electric power.  The Branch Circuit supplying this receptacle(s) shall not supply outlets outside the garage.  At least _______ receptacle(s) outlet shall be installed for each car space.

a) one
b) two
c) three
d) four



Final Elapsed Time at submittal:



Go to top of quiz
© Gerald Newton