1. |
The circuit conductor that is defined as being intentionally grounded is the _______ conductor.
|
|
|
|
|
a)
|
|
grounding |
b)
|
|
grounded |
c)
|
|
equipment grounding |
d)
|
|
grounding electrode |
|
|
|
|
|
|
2. |
Class II location are those that are hazardous because of the presence of ________.
|
|
|
|
|
a)
|
|
ignitable vapors |
b)
|
|
ignitable fibers |
c)
|
|
combustible dust |
d)
|
|
combustible liquids |
|
|
|
|
|
|
3. |
If three resistors with values 5, 10, and 15 ohms respectively are connected in parallel, the combined total resistance is ____ ohms. Select the closest answer.
|
|
|
|
|
a)
|
|
0.4 |
b)
|
|
2.3 |
c)
|
|
2.7 |
d)
|
|
30.0 |
|
|
|
|
|
|
4. |
The wiring in a 200 foot long branch circuit measures a total resistance of 0.5 ohms. What is the resistance per 1,000 feet?
|
|
|
|
|
a)
|
|
0.5 ohms |
b)
|
|
1.0 ohms |
c)
|
|
2.5 ohms |
d)
|
|
5.0 ohms |
|
|
|
|
|
|
5. |
The maximum total voltage drop on both feeders and branch circuits to the farthest outlet should not exceed ____ percent of the supply voltage.
|
|
|
|
|
a)
|
|
2 |
b)
|
|
3 |
c)
|
|
4 |
d)
|
|
5 |
|
|
|
|
|
|
6. |
The maximum total voltage drop on a feeder and branch circuit to the farthest outlet should not exceed _____ percent.
|
|
|
|
|
a)
|
|
2 |
b)
|
|
5 |
c)
|
|
4 |
d)
|
|
3 |
|
|
|
|
|
|
7. |
For dwelling units, the Code requires a minimum of _______ for the kitchen small appliance load.
|
|
|
|
|
a)
|
|
one 15 ampere |
b)
|
|
two 15 ampere circuits |
c)
|
|
one 20 ampere circuit |
d)
|
|
two 20 ampere circuits |
|
|
|
|
|
|
8. |
Generally, equipment grounding conductors No. 6 and smaller shall be identified by ______.
(select best answer) |
|
|
|
|
a)
|
|
green color unless it is bare |
b)
|
|
green color with one or more yellow stripes unless it
is bare |
c)
|
|
bare conductor |
d)
|
|
bare or Individually covered or insulated equipment
grounding conductors shall have a continuous outer finish that is
either green or green with one or more yellow stripes except as permitted
in this section. |
e)
|
|
All of the above |
|
|
|
|
|
|
9. |
Rod and pipe grounding electrodes shall not be less than ____ feet in length.
|
|
|
|
|
a)
|
|
6 |
b)
|
|
7 |
c)
|
|
8 |
d)
|
|
10 |
|
|
|
|
|
|
10. |
Every dining room of a dwelling unit requires receptacle outlets to be installed so that no point along the floor line in any wall space more than _____ feet, measured horizontally, from an outlet.
|
|
|
|
|
a)
|
|
6 |
b)
|
|
7 |
c)
|
|
8 |
d)
|
|
10 |
|
|
|
|
|
|
11. |
Open runs of Listed liquidtight
flexible nonmetallic conduit installed in lengths longer then ____
feet shall be secured every ____ feet. |
|
|
|
|
a)
|
|
6, 3 |
b)
|
| 6, 4 1/2 |
c)
|
| 6, 66 |
d)
|
| 10, 10 |
|
|
|
|
|
|
12. |
Generally, noncurrent-carrying metal parts of electrical equipment should be kept at least ____ feet away from lightning rod conductors in air and 3 feet from lightning conductors in concrete, or shall be bonded to the lightning conductors.
|
|
|
|
|
a)
|
| 3 |
b)
|
| 4 |
c)
|
| 5 |
d)
|
| 6 |
|
|
|
|
|
|
13. |
Branch-circuit conductors supplying a single motor which operates under continuous duty shall have an ampacity not less than ____ percent of the motor full-load current rating.
|
|
|
|
|
a)
|
| 100 |
b)
|
| 115 |
c)
|
| 125 |
d)
|
| 140 |
|
|
|
|
|
|
14. |
The maximum number of overcurrent devices (other than those provided in the mains) in a single cabinet of a lighting and appliance panelboard shall be ____.
|
|
|
|
|
a)
|
| 30 |
b)
|
| 36 |
c)
|
| 42 |
d)
|
| 46 |
|
|
|
|
|
|
15. |
Where a branch circuit supplies
continuous loads or any combination of continuous and noncontinuous
loads, the minimum branch-circuit conductor size, before the application
of any adjustment or correction factors, shall have an allowable ampacity
not less than the noncontinuous load plus ______ percent of the continuous
load. |
|
|
|
|
a)
|
| 65 |
b)
|
|
80 |
c)
|
|
125 |
d)
|
|
200 |
|
|
|
|
|
|
16. |
Liquid-tight flexible metal conduit may be used in _____.
|
|
|
|
|
a)
|
| areas that are both exposed and concealed |
b)
|
| areas that are subject to physical damage |
c)
|
| 4 1/2 inch trade size |
d)
|
| 5 inch trade size |
|
|
|
|
|
|
17. |
The maximum size of flexible metallic tubing that may be used in any construction or installation is _____.
|
|
|
|
|
a)
|
| 3/8" |
b)
|
| 1/2" |
c)
|
| 3/4" |
d)
|
| 1" |
|
|
|
|
|
|
18. |
Where conductors of less than 600 volts emerge from the ground they shall be protected by enclosures or raceways that extend from below grade to a point at least ____ feet above finished grade.
|
|
|
|
|
a)
|
| 4 |
b)
|
| 6 |
c)
|
| 8 |
d)
|
| 10 |
|
|
|
|
|
|
19. |
The total number of quarter bends allowed in one run of rigid nonmetallic conduit shall not exceed ____.
|
|
|
|
|
a)
|
| 2 |
b)
|
| 3 |
c)
|
| 4 |
d)
|
| 5 |
|
|
|
|
|
|
20. |
Where ungrounded conductors of minimum size No. _____ or larger enter a raceway in a cabinet, the conductors shall be protected by an insulated fitting.
|
|
|
|
|
a)
|
| 3 |
b)
|
| 4 |
c)
|
| 6 |
d)
|
| 5 |
|
|
|
|
|
|