1. |
Several motors, each not exceeding 1 hp in rating, shall be permitted on a nominal 120-volt branch circuit protected at not over 20 amperes or a branch circuit of 600 volts, nominal, or less, protected at not over 15 amperes, if which of the following conditions are met.
|
|
|
|
|
|
a)
|
The full-load rating of each motor does not exceed 6 amperes
|
|
b)
|
The rating of the branch-circuit short-circuit and ground-fault protective device marked on any of the controllers is not exceeded.
|
|
c)
|
Individual overload protection conforms to Section 430-32.
|
|
d)
|
All of the above
|
|
|
|
|
|
|
2. |
Where conductors are run in parallel in parallel raceways the grounding conductors shall be_______.
|
|
|
|
|
|
a)
|
run in parallel
|
|
b)
|
run in at least one raceway
|
|
c)
|
run in an isolated raceway
|
|
d)
|
run outside the raceways but secured to the raceway.
|
|
|
|
|
|
|
3. |
Taps to brake coils of cranes and hoists shall be protected by _____.
|
|
|
|
|
|
a)
|
20 amperes circuit breaker
|
|
b)
|
15 ampere fuses
|
|
c)
|
10 ampere fuses
|
|
d)
|
Nothing. No protection is required.
|
|
|
|
|
|
|
4. |
The ampere rating of the disconnecting means serving a hermetic refrigerant motor-compressor shall be ______ of the nameplate rated-load current or branch-circuit selection current, whichever is greater
|
|
|
|
|
|
a)
|
115 percent
|
|
b)
|
125 percent
|
|
c)
|
135 percent
|
|
|
|
|
|
|
5. |
Underground wiring for bulk storage plants is permitted to be installed in _______
|
|
|
|
|
|
a)
|
threaded rigid metal conduit
|
|
b)
|
threaded steel intermediate metal conduit
|
|
c)
|
where buried under not less than 2 ft (610 mm) of cover, shall be permitted in rigid nonmetallic conduit or an approved cable
|
|
d)
|
All of the above
|
|
|
|
|
|
|
6. |
Disregarding any exceptions the fixed wiring method for theatres that have an occupancy load of 100 persons or more shall be _______.
|
|
|
|
|
|
a)
|
Nonmetallic sheathed cable
|
|
b)
|
Electrical nonmetallic tubing
|
|
c)
|
The fixed wiring methods shall be metal raceways, flexible metal raceways, nonmetallic raceways encased in not less than 2 in. of concrete, Type MI, MC, or AC cable containing an insulated equipment grounding conductor.
|
|
d)
|
All of the above
|
|
|
|
|
|
|
7. |
What is the minimum number of duplex receptacles required for each patient bed in the critical care area of a hospital.
|
|
|
|
|
|
a)
|
1
|
|
b)
|
2
|
|
c)
|
3
|
|
|
|
|
|
|
8. |
When there is a power outage in a hospital and the automatic switching equipment is activated to emergency service what is the required time delay setting for re-establishing the normal service after normal service power is restored.
|
|
|
|
|
|
a)
|
Not more than 10 seconds
|
|
b)
|
30 seconds
|
|
c)
|
5 minutes
|
|
d)
|
15 minutes
|
|
|
|
|
|
|
9. |
An operating room in a hospital where the use of non-flammable anesthetizing agents are used, the area is classified as a(n) _______ location.
|
|
|
|
|
|
a)
|
Class I, Division I
|
|
b)
|
Class I, Division 2
|
|
c)
|
non-hazardous location
|
|
|
|
|
|
|
10. |
Splices and taps are permitted in wireways provided they are accessible and do not fill the wireway to more than _____ percent of the cross sectional area and are ________..
|
|
|
|
|
|
a)
|
50, accessible
|
|
b)
|
60, accessible
|
|
c)
|
75, accessible
|
|
d)
|
80, accessible
|
|
|
|
|
|
|
11. |
Both metallic and nonmetallic wireways can be filled to 20 percent of their cross sectional area, but the following statement is true about their differences._
|
|
|
|
|
|
a)
|
No derating of over 3 current carrying conductors apply to nonmetallic wireways but not to metallic wireways.
|
|
b)
|
There is no derating of up to 30 current carrying conductors in metallic wireway but there is derating for over 3 current carrying conductors in a nonmetallic wireway.
|
|
c)
|
There is no derating for up to 30 current carrying conductors in metallic and nonmetallic wireways.
|
|
|
|
|
|
|
12. |
Refer to the figure below. The current through R2 is _____ . (select the closest answer)
|
|
|
|
|
|
a)
|
2.7 amperes
|
|
b)
|
1.3 amperes
|
|
c)
|
5.7 amperes
|
|
d)
|
8.3 amperes
|
|
|
|
|
|
|
13. |
Performance standard(s) that transfer equipment used in emergency systems shall meet is:
|
|
|
|
|
|
a)
|
Automatic transfer switches shall be electrically operated and mechanically held.
|
|
b)
|
Transfer equipment shall be designed and installed to prevent the inadvertent interconnection of normal and emergency sources of supply in any operation of the transfer equipment.
|
|
c)
|
Transfer equipment shall supply only emergency loads.
|
|
d)
|
All of the above
|
|
|
|
|
|
|
14. |
In a run of underground rigid metal conduit from a gasoline dispenser to the service panelboard in a nonhazardous location a total of ____sealoffs are required.
|
|
|
|
|
|
a)
|
1
|
|
b)
|
2
|
|
c)
|
3
|
|
d)
|
4
|
|
|
|
|
|
|
15. |
In general, direct burial cable rated above _____ volts shall be shielded.
|
|
|
|
|
|
a)
|
12,000
|
|
b)
|
5,000
|
|
c)
|
2,400
|
|
d)
|
2,000
|
|
|
|
|
|
|
16. |
In a hospital general care area each patient bed location shall be provided with a minimum of ____ receptacles.
|
|
|
|
|
|
a)
|
1 duplex
|
|
b)
|
3 duplex or 6 single
|
|
c)
|
2 duplex or 4 single.
|
|
d)
|
4 duplex
|
|
|
|
|
|
|
17. |
Where a surface-mounted fixture containing a ballast is to be installed on combustible low-density cellulose fiberboard, it shall be listed for this condition or shall be spaced not less than _______ in. from the surface of the fiberboard.
|
|
|
|
|
|
a)
|
1/4
|
|
b)
|
3/8
|
|
c)
|
1 1/2
|
|
d)
|
2
|
|
|
|
|
|
|
18. |
What is the minimum size equipment bonding jumper required for a raceway containing a circuit protected at 60 amperes.
|
|
|
|
|
|
a)
|
No. 14
|
|
b)
|
No. 12
|
|
c)
|
No. 10
|
|
d)
|
No. 8
|
|
|
|
|
|
|
19. |
An individual outlet with taps not over 18 inches long is connected to a 50 ampere circuit to supply a household kitchen wall-mounted oven. The tap conductor ampacity shall not be less than _____ amperes.
|
|
|
|
|
|
a)
|
50
|
|
b)
|
40
|
|
c)
|
30
|
|
d)
|
20
|
|
|
|
|
|
|
20. |
Given an AC transformer and DC rectifier arc welder with a 60 percent duty cycle. The ampacity of the supply conductors shall be calculated by multiplying the nameplate current by a factor of _______.
|
|
|
|
|
|
a)
|
.78
|
|
b)
|
.84
|
|
c)
|
.89
|
|
|
|
|
|
|