1. |
An applied voltage of 10 percent below rating can result in a decrease in efficiency of substantially more than 10 percent — for example, fluorescent light output would be reduced by 15 percent, and incandescent light output would be reduced by __________ . Induction motors would run hotter and produce less torque.
|
|
|
|
|
|
|
|
|
a)
|
10 percent
|
|
b)
|
30 percent
|
|
c)
|
40 percent
|
|
|
|
|
|
|
2. |
Energy costs can be _________ by decreasing voltage drop.
|
|
|
|
|
|
|
|
|
a)
|
lowered
|
|
b)
|
eliminated
|
|
c)
|
increased
|
|
|
|
|
|
|
3. |
Article 647 states that for Sensitive Electronic Equipment the voltage drop on branch circuits supplying equipment connected using wiring methods in Chapter 3 shall not exceed _________ and the combined voltage drop of feeder and branch-circuit conductors shall not exceed __________ .
|
|
|
|
|
|
|
|
|
a)
|
5 percent, 2.5 percent
|
|
b)
|
3 percent, 5 percent
|
|
c)
|
1.5 percent, 2.5 percent
|
|
|
|
|
|
|
4. |
By NEC Article 645 for fire pumps the voltage at the controller line terminals shall not drop more than _________ below normal (controller-rated voltage) under motor starting conditions. The voltage at the motor terminals shall not drop more than _________ below the voltage rating of the motor when the motor is operating at 115 percent of the full-load current rating of the motor.
|
|
|
|
|
|
|
|
|
a)
|
5 percent, 3 percent
|
|
b)
|
15 percent, 3 percent
|
|
c)
|
15 percent, 5 percent
|
|
|
|
|
|
|
5. |
The energy Code has strict requirements and limits the voltage drop on branch circuits for the run from the final circuit breaker to the outlet or load to _______ maximum voltage drop allowed at design load and limits the voltage drop for the run between the service entrance equipment and the branch circuit distribution equipment to _______ maximum voltage drop allowed at design load.
|
|
|
|
|
|
|
|
|
a)
|
3 percent, 2 percent
|
|
b)
|
2 percent, 5 percent
|
|
c)
|
5 percent, 4 percent
|
|
|
|
|
|
|
6. |
The effect of a power factor equal to 0.85 for 3 each 3-phase 500 kcmil conductors in a steel raceway increases voltage drop by ____________than the direct current method of calculation.
|
|
|
|
|
|
|
|
|
a)
|
94 percent more
|
|
b)
|
94 percent less
|
|
c)
|
100 percent more
|
|
|
|
|
|
|
7. |
There are several ways to decrease voltage drop. They include:
|
|
|
|
|
|
|
|
|
a)
|
using larger size conductors
|
|
b)
|
shortening the circuit length
|
|
c)
|
decreasing the circuit load
|
|
d)
|
for decreasing voltage drop to neutral by balancing the load for 3-phase, 4 wire systems
|
|
e)
|
All of the above
|
|
|
|
|
|
|
8. |
If power factor is not close to 1.0 voltage drop for 3 phase 3 wire circuits in raceway can be found using information from _______ of the NEC.
|
|
|
|
|
|
|
|
|
a)
|
Table 8
|
|
b)
|
Table 9
|
|
c)
|
Table 10
|
|
|
|
|
|
|
9. |
When we use the direct current method of finding voltage drop we can use the resistances from Table 8 of the NEC or use the following equation: (where L is one way circuit length)
|
|
|
|
|
|
|
|
|
a)
|
VD = (2KLI/CMA) x multiplier
|
|
b)
|
VD = (KLI/CMA) x multiplier
|
|
c)
|
VD = (KLI/CMA)
|
|
|
|
|
|
|
10. |
By Table 8 of the NEC the resistance of 1000 feet of No. 10 copper stranded conductor is _______ .
|
|
|
|
|
|
|
|
|
a)
|
1.24 ohms
|
|
b)
|
1.21 ohms
|
|
c)
|
2.04 ohms
|
|
|
|
|
|
|