|
||
Transformer Protection
For transformer protection, fuses must be
rated not over 3.0 x .73 Amperes or 2.0 Amperes. shall be placed in EACH
ungrounded conductor per 240.20(A). Grounding of Secondary Circuit
|
Secondary Conductor Protection
The secondary conductors are protected according to Section 725.24(D): "Class 1 circuit conductors supplied by the secondary of a single-phase transformer having only a 2-wire (single-voltage) secondary shall be permitted to be protected by overcurrent protection provided on the primary side of the transformer, provided this protection is in accordance with 450.3 and does not exceed the value determined by multiplying the secondary conductor ampacity by the secondary-to-primary transformer voltage ratio. Transformer secondary conductors other than 2 wire shall not be considered to be protected by the primary overcurrent protection. ." For the above problem this converts to: (24/480) x (20) <= 1 ampere |