"250.112(I) Power-Limited Remote-Control, Signaling,
and Fire Alarm Circuits. Equipment supplied by Class 1 power-limited
circuits and Class 1, Class 2, and Class 3 remote-control and signaling circuits,
and by fire alarm circuits, shall be grounded where system grounding is required
by Part II or Part VIII of this article."
For AC circuits that are 50 volts or less: "250.20(A)
Alternating-Current Circuits of Less Than 50 Volts. Alternating-current circuits
of less than 50 volts shall be grounded under any of the following conditions:
(1) Where supplied by transformers, if the transformer supply system exceeds
150 volts to ground
(2) Where supplied by transformers, if the transformer supply system is ungrounded
(3) Where installed as overhead conductors outside of buildings"
However, SHORT SECTIONS OF RACEWAY, do not always have to
be grounded. Section 250.86 Exception No. 2 - "Short Sections of metal enclosures
used to provide support or protection of cable assemblies from physical damage
shall not be required to be grounded."
|