|
History
Since 1889, many individuals and organizations have attempted to find the
correct ampacity for conductors so they would not overheat and ruin the
insulations. In 1889 Kennelly published one of the first tables listing 46
amperes as the ampacity of a number 10 conductor. In 1890 Fisher listed 19.1
amperes, and in 1894 the insurance industry listed 20 amperes as the ampacity
for the same conductor. But that was not the end of it. By 1937 there were 16
ampacities discovered for the same size conductor. In 1938 Samuel J. Rosch, an
associate member of the American Institute of Electrical Engineers and the
manager of insulated products development for the Anaconda Wire and Cable
Company, conducted a thorough investigation to find the correct ampacities for
all the standard size conductors used at that time. To establish the maximum
prolonged operating temperature for insulations, he performed aging and
elongation tests in environmental ovens. He built a structure, wired it,
embedded thermocouples in the conductors, and applied voltages and measured the
ampacities and temperatures. He published his findings in a paper titled, "The
Current-Carrying Capacity of Rubber-Insulated Conductors" delineating the
results of his experiments. His work resulted in a table XI that became Table
310-16 of the National Electrical Code. Rosch's original table was based on an
ambient temperature of 30 degrees centigrade and a conductor temperature of 50
degrees centigrade for code grade rubber, the type of insulation used in those
days. If we convert the ampacities in table XI to 60 degrees centigrade using
the formula given in note 1 to tables 310-69 through 310-84, setting delta TD
equal to 0 (delta TD is for high voltages: we are only concerned with 600 volts
and under), and rounding off to the nearest 5 amperes, we can calculate the
ampacities for 60 degree insulations as found in the first column of table
310-16. Likewise, the same calculation can determine the the ampacities for the
75 degree and 90 degree columns in table 310- 16.
Faults with Table 310-16
There are three very important deficiencies in Rosch's paper. First, he
did not investigate the effects of proximal heating from adjacent conduits,
ducts, and duct banks. Secondly, his experiments were only for above ground
installations. Thirdly, the heat produced by high voltages was not
investigated. But for most applications when load calculations are performed
according to Article 220, there is enough safety margin built in to preclude any
problems. To explain this, a fine print note was added to section 310-15(a) in
the 1990 NEC stating that Tables 310-16 through 310-19 are application tables
that are for use in determining conductor sizes on loads calculated in
accordance with Article 220. When calculating loads per article 220 a
substantial safety margin is included as opposed to some engineering
calculations that calculate the "actual" load.
The deficiencies to Table 310- 16 became a problem in the 1950's when
Americans began installing very large air conditioning systems in the the larger
buildings, using underground service laterals run in massive underground duct
banks. In cases where engineers performed load calculations using engineering
methods in place of Article 220, and used Table 310-16 to determine the size of
conductors, conductors overheated and burned open, especially the conductors
located near the center of the duct banks. Rosch used a basic heat transfer
equation with the addition of a term "n" for the number of conductors
in the same cable or raceway. But there were no terms in his equation to adjust
the ampacity for heat that came from adjacent ducts and duct banks, or for the
differences for heat dissipation in an underground installation. Later
calculations using the Neher-McGrath equation found in 310-15(b) of the NEC
would determine that the center conductors in a 3 by 3 duct banks must be
derated to almost 60 percent because of the proximal heating effect from
adjacent ducts and duct banks.
To develope a more accurate method of finding the ampacity of conductors in
underground installations two cable engineers, in 1957, developed the
Neher-McGrath
equation found in 310-15(c) of the 1999 NEC.
|